Allen-Bradley Flex IO 1794-AENT/B ENIP Request Path Network Segment Denial of Service Vulnerability
A specially crafted ENIP request containing a reserved Network Segment sub-type causes the Allen-Bradley Flex IO 1794-AENT/B to enter a fault state. An attacker can send such a packet to cause loss of communications with the device, requiring a physical power cycle.
Originally disclosed on Cisco Talos
An exploitable denial of service vulnerability exists in the ENIP Request Path Network Segment functionality of Allen-Bradley Flex IO 1794-AENT/B. A specially crafted network request can cause a loss of communications with the device resulting in denial-of-service.
The full write-up lives on its author's site
It belongs to its author, so we link to it rather than copy it. The other two tabs are our own rewrites, checked against it.
Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.
How it worked
Root cause
Likely the device does not validate that the Network Segment Length in words fits within the remaining packet data before using it.
Impact
An unauthenticated attacker on the network can cause a denial of service, losing communication with the device until it is physically power-cycled.
What the attacker needed
Network access to the device; no authentication required
How it was found
- Send an ENIP SendRRData command with an encapsulated unconnected message.
- Include a Request Path containing a Network Segment with a reserved sub-type between 0x50 and 0x5f.
- Set the following byte as the Network Segment Length in words to a value larger than the remaining packet data.
- The device enters a fault state and communication is lost until a physical power cycle.
Explained by bugbounty.wiki with AI from the original and checked against quotes from it; it can still be wrong. Read the original before relying on a detail.
Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.
This is a denial-of-service bug in an industrial network device. The device reads a length value from an incoming message and trusts it, so a malformed message makes it crash and stop talking on the network. Someone has to power-cycle the hardware by hand to bring it back.
What is DoS?
A request that exhausts resources or crashes a component. Many programs forbid testing it; reports usually show it from code, not by attacking.