Schneider Electric Modicon M580 HTTP Request Denial of Service Vulnerability
An unauthenticated attacker can send an HTTP request to an existing resource during the HTTP server's initialisation, causing the device to enter a non-recoverable fault state and stop all remote communications. The device requires a physical power cycle to recover.
Originally disclosed on Cisco Talos
An exploitable denial of service vulnerability exists in the HTTP request processing of the Schneider Electric Modicon M580 Programmable Automation Controller firmware version SV2.70. An appropriately timed HTTP request can cause the device to enter a non-recoverable fault state, resulting in a complete stoppage of…
The full write-up lives on its author's site
It belongs to its author, so we link to it rather than copy it. The other two tabs are our own rewrites, checked against it.
Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.
How it worked
Root cause
Likely an uncaught exception occurs when an HTTP request arrives during the HTTP server's initialisation, leading to a non-recoverable fault.
Impact
The device enters a non-recoverable fault state, stopping all remote communications and process logic execution, and requires a physical power cycle to recover.
What the attacker needed
Network access to the device; request timed during HTTP server initialisation
The fix
The vendor patched the vulnerability.
How it was found
- Send an HTTP GET request to an existing resource on the device.
- Time the request to arrive during the HTTP server's initialisation process.
- The device enters a non-recoverable fault state and stops all remote communications.
Explained by bugbounty.wiki with AI from the original and checked against quotes from it; it can still be wrong. Read the original before relying on a detail.
Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.
This is a denial-of-service bug in an industrial controller. If someone sends a normal web request at the exact moment the device's web server is starting up, the device crashes into an error mode and stops talking to anything remotely. The only way to fix it is to physically power-cycle the device.
What is DoS?
A request that exhausts resources or crashes a component. Many programs forbid testing it; reports usually show it from code, not by attacking.