Skip to content
DoS Advisory Intermediate CVE-2019-6847

Schneider Electric Modicon M580 outdated firmware image FTP upgrade denial-of-service vulnerability

The FTP firmware update functionality of the Schneider Electric Modicon M580 programmable automation controller can be tricked into accepting an outdated firmware image, causing the device to enter a non-recoverable fault state. An attacker with default FTP credentials can send commands to trigger this, resulting in a complete stoppage of remote communications.

Jared Rittle Follow

Originally disclosed on Cisco Talos

Medium 4.9 View original

An exploitable denial-of-service vulnerability exists in the FTP firmware update functionality of the Schneider Electric Modicon M580 Programmable Automation Controller, firmware version SV2.80. An outdated firmware image can cause the device to enter a non-recoverable fault state, resulting in a complete stoppage of…

Jared Rittle, on Cisco Talos

The full write-up lives on its author's site

It belongs to its author, so we link to it rather than copy it. The other two tabs are our own rewrites, checked against it.

Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.

How it worked

Root cause

Likely the firmware upgrade process does not properly validate the version or integrity of the uploaded firmware image, leading to an uncaught exception when an outdated image is used.

Impact

The device enters a non-recoverable fault state, stopping all remote communications and process logic execution, and requires physical USB access to recover.

What the attacker needed

Default FTP credentials; network access to FTP service; outdated firmware image

How it was found

  1. Log in to the device's FTP service using default credentials.
  2. Send required FTP commands to prepare the device.
  3. Delete any existing firmware files and directories to avoid state issues.
  4. Create the necessary directory structure for the firmware upgrade.
  5. Upload the outdated firmware files to the device.
  6. Send the custom FTP command to start the firmware upgrade, causing the device to fault.

Explained by bugbounty.wiki with AI from the original and checked against quotes from it; it can still be wrong. Read the original before relying on a detail.

Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.

A programmable automation controller (PAC) is an industrial computer that controls machinery. This report shows that if someone with the default login uploads an old version of the PAC's firmware (its operating software) using the file transfer protocol (FTP), the device can crash so badly that it stops responding and must be fixed by physically connecting to it. The attacker needs to know the default username and password, which are often left unchanged.

What is DoS?

A request that exhausts resources or crashes a component. Many programs forbid testing it; reports usually show it from code, not by attacking.

More by Jared Rittle

View all

64 more disclosed reports, best first.

More from Cisco Talos

View all

The newest disclosed reports for this program.

Similar reports

View all

Same bug class and techniques, clearest first.

Denial of service

The lesson behind this report.

A request that exhausts resources or crashes a component. Many programs forbid testing it; reports usually show it from code, not by attacking.