Schneider Electric Modicon M580 UMAS function code 0x65 denial-of-service vulnerability
A denial-of-service vulnerability exists in the UMAS function code 0x65 of the Schneider Electric Modicon M580 PLC. An unauthenticated attacker can send a specially crafted command to put the device into a non-recoverable fault state, stopping all remote communications and requiring a physical power cycle.
Originally disclosed on Cisco Talos
An exploitable denial-of-service vulnerability exists in the UMAS function code 0x65 functionality of the Schneider Electric Modicon M580 Programmable Automation Controller, firmware version SV2.70. A specially crafted UMAS command can cause the device to enter a non-recoverable fault state, resulting in a complete…
The full write-up lives on its author's site
It belongs to its author, so we link to it rather than copy it. The other two tabs are our own rewrites, checked against it.
Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.
How it worked
Root cause
Likely the device fails to validate the length or content of the data payload in UMAS function code 0x65, leading to an uncaught exception when a specific byte value is present.
Impact
The device enters a non-recoverable fault state, causing a complete stoppage of remote communications and process logic execution, requiring a physical power cycle to recover.
What the attacker needed
Network access to the PLC on TCP port 502; no authentication required
The fix
The vendor patched the vulnerability.
How it was found
- Connect to the PLC on TCP port 502.
- Send a UMAS command to obtain a PLC reservation and extract the session identifier from the response.
- Send a UMAS function code 0x65 command with a data payload of at least 0x10 bytes where the 13th byte is 0xff.
- The device enters a non-recoverable fault state and stops responding.
Explained by bugbounty.wiki with AI from the original and checked against quotes from it; it can still be wrong. Read the original before relying on a detail.
Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.
This is a denial-of-service bug in an industrial controller. An attacker can send a malformed network message that crashes the device, making it stop responding until someone manually restarts it. No login is needed, so anyone who can reach the device on the network can cause the disruption.
What is DoS?
A request that exhausts resources or crashes a component. Many programs forbid testing it; reports usually show it from code, not by attacking.