Schneider Electric Modicon M580 UMAS function code 0x6d multiple denial-of-service vulnerabilities
Multiple denial-of-service vulnerabilities exist in the UMAS protocol of the Schneider Electric Modicon M580 controller. An unauthenticated attacker can send specially crafted UMAS commands to cause the device to enter a fault state, stopping remote communications and process execution.
Originally disclosed on Cisco Talos
Multiple denial-of-service vulnerabilities exist in the UMAS protocol functionality of the Schneider Electric Modicon M580 Programmable Automation Controller, firmware version SV2.70. Specially crafted UMAS commands can cause the device to enter a non-recoverable fault state, resulting in a complete stoppage of remote…
The full write-up lives on its author's site
It belongs to its author, so we link to it rather than copy it. The other two tabs are our own rewrites, checked against it.
Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.
How it worked
Root cause
Likely, the UMAS protocol handler fails to properly validate specific function code and subcode combinations, leading to uncaught exceptions that crash the device.
Impact
An attacker could cause a denial-of-service condition, requiring a physical power cycle or programming software to recover the device.
What the attacker needed
Network access to port 502; no authentication required
The fix
The vendor patched the vulnerabilities.
How it was found
- Connect to the device on TCP port 502.
- Send a UMAS command with function code 0x6d and specific subcodes (e.g., 0x00/0x80, 0x00/0xf9, 0x01/0x8b then 0x01/0x86, 0x78, or 0x79).
- Observe the device entering a fault state, stopping communications and process execution.
Explained by bugbounty.wiki with AI from the original and checked against quotes from it; it can still be wrong. Read the original before relying on a detail.
Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.
This report describes flaws in a programmable logic controller (PLC), a computer used to control machinery. By sending malformed network messages, an attacker can crash the device, stopping its control over equipment and cutting off remote access. The device must be manually power-cycled to recover.
What is DoS?
A request that exhausts resources or crashes a component. Many programs forbid testing it; reports usually show it from code, not by attacking.