Skip to content
DoS Advisory Intermediate CVE-2018-7843

Schneider Electric Modicon M580 UMAS memory block read denial-of-service vulnerability

A denial-of-service vulnerability exists in the UMAS memory block read function of the Schneider Electric Modicon M580 controller. An unauthenticated attacker can send a crafted command to cause a non-recoverable fault, stopping all remote communications and requiring a physical power cycle.

Jared Rittle Follow

Originally disclosed on Cisco Talos

High 7.5 View original

An exploitable denial-of-service vulnerability exists in the UMAS memory block read function of the Schneider Electric Modicon M580 programmable automation controller, firmware version SV2.70. A specially crafted UMAS command can cause the device to enter a non-recoverable fault state, resulting in a complete stoppage…

Jared Rittle, on Cisco Talos

The full write-up lives on its author's site

It belongs to its author, so we link to it rather than copy it. The other two tabs are our own rewrites, checked against it.

Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.

How it worked

Root cause

Likely the device does not properly validate the size and offset fields in the MEMORY_BLOCK_READ command, allowing reads beyond the end of a memory block and causing an uncaught exception.

Impact

The device enters a non-recoverable fault state, stopping all remote communications and process logic execution, and requires a physical power cycle to recover.

What the attacker needed

Network access to the device on port 502; no authentication required

The fix

The vendor patched the vulnerability.

How it was found

  1. Connect to the device on TCP port 502.
  2. Send a MEMORY_BLOCK_READ command with block 0x8032 or 0x8033 and a data size of at least 0x01 bytes.
  3. Alternatively, send a MEMORY_BLOCK_READ command for block 0x00 with an offset of at least 0x2fff.
  4. Observe the device entering a non-recoverable fault state.

Explained by bugbounty.wiki with AI from the original and checked against quotes from it; it can still be wrong. Read the original before relying on a detail.

Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.

This is a denial-of-service bug in an industrial controller. An attacker can send a special network message that makes the device crash and stop working until someone manually power-cycles it. No login is needed, so anyone who can reach the device on the network can do this.

What is DoS?

A request that exhausts resources or crashes a component. Many programs forbid testing it; reports usually show it from code, not by attacking.

More by Jared Rittle

View all

64 more disclosed reports, best first.

More from Cisco Talos

View all

The newest disclosed reports for this program.

Similar reports

View all

Same bug class and techniques, clearest first.

Denial of service

The lesson behind this report.

A request that exhausts resources or crashes a component. Many programs forbid testing it; reports usually show it from code, not by attacking.