Schneider Electric Modicon M580 UMAS memory block write denial-of-service vulnerability
A denial-of-service vulnerability exists in the UMAS memory block write functionality of the Schneider Electric Modicon M580 controller. An unauthenticated attacker can send a specially crafted UMAS command with large offset and size values to cause the device to enter a non-recoverable fault state, stopping all remote communications and requiring a physical power cycle.
Originally disclosed on Cisco Talos
An exploitable denial-of-service vulnerability exists in the UMAS memory block write functionality of the Schneider Electric Modicon M580 Programmable Automation Controller, firmware version SV2.70. A specially crafted UMAS command can cause the device to enter a non-recoverable fault state, resulting in a complete…
The full write-up lives on its author's site
It belongs to its author, so we link to it rather than copy it. The other two tabs are our own rewrites, checked against it.
Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.
How it worked
Root cause
Likely the device fails to validate the offset and size values in UMAS memory block write commands, leading to an uncaught exception and a non-recoverable fault.
Impact
An unauthenticated attacker can cause a complete denial of service, stopping all remote communications and process logic execution until the device is physically power-cycled.
What the attacker needed
Network access to the device on TCP port 502; no authentication required
The fix
The vendor patched the vulnerability, as indicated in the timeline.
How it was found
- Connect to the device on TCP port 502.
- Send a UMAS memory block write command specifying an affected block number and large offset and size values.
- The device enters a non-recoverable fault state and stops all remote communications.
Explained by bugbounty.wiki with AI from the original and checked against quotes from it; it can still be wrong. Read the original before relying on a detail.
Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.
This report describes a flaw in an industrial controller that lets anyone on the network crash it by sending a single malformed network message. The message tells the device to write to a memory block using an offset and size that are too large, and the device does not handle this gracefully, so it stops working until someone physically restarts it. No login is needed, making it easy to disrupt operations.
What is DoS?
A request that exhausts resources or crashes a component. Many programs forbid testing it; reports usually show it from code, not by attacking.