Skip to content
DoS Advisory Intermediate CVE-2019-6809

Schneider Electric Modicon M580 UMAS read strategy denial-of-service vulnerability

A denial-of-service vulnerability exists in the UMAS read strategy functionality of the Schneider Electric Modicon M580 controller. An attacker can send unauthenticated UMAS commands with a small block length and multiple block requests to cause a non-recoverable fault, stopping all remote communications and requiring a physical power cycle.

Jared Rittle Follow

Originally disclosed on Cisco Talos

High 7.5 View original

An exploitable denial-of-service vulnerability exists in the UMAS read strategy functionality of the Schneider Electric Modicon M580 programmable automation controller, firmware version SV2.70. A specially crafted set of UMAS commands can cause the device to enter a non-recoverable fault state, resulting in a complete…

Jared Rittle, on Cisco Talos

The full write-up lives on its author's site

It belongs to its author, so we link to it rather than copy it. The other two tabs are our own rewrites, checked against it.

Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.

How it worked

Root cause

Likely the device does not properly validate the block length field in the INITIALIZE_DOWNLOAD command, leading to an uncaught exception when a small length is used with multiple block requests.

Impact

The device enters a non-recoverable fault state where all remote communications stop, process logic stops, and a physical power cycle is required to restore functionality.

What the attacker needed

Network access to the device on port 502; no authentication required

The fix

The vendor patched the vulnerability; the report does not detail the fix.

How it was found

  1. Connect to the device on TCP port 502.
  2. Send an INITIALIZE_DOWNLOAD UMAS command with a block length of zero.
  3. Send at least four DOWNLOAD_BLOCK UMAS commands.
  4. Observe the device entering a non-recoverable fault state.

Explained by bugbounty.wiki with AI from the original and checked against quotes from it; it can still be wrong. Read the original before relying on a detail.

Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.

This report describes a flaw in an industrial controller that lets anyone send a few network messages to crash it. The device stops responding and must be manually power-cycled to work again. No login is needed, so an attacker on the network can cause disruption.

What is DoS?

A request that exhausts resources or crashes a component. Many programs forbid testing it; reports usually show it from code, not by attacking.

More by Jared Rittle

View all

64 more disclosed reports, best first.

More from Cisco Talos

View all

The newest disclosed reports for this program.

Similar reports

View all

Same bug class and techniques, clearest first.

Denial of service

The lesson behind this report.

A request that exhausts resources or crashes a component. Many programs forbid testing it; reports usually show it from code, not by attacking.