Skip to content
DoS Advisory Intermediate CVE-2019-6828

Schneider Electric Modicon M580 UMAS Read System Coils and Registers Denial of Service Vulnerability

A denial of service vulnerability exists in the UMAS Read System Coils and Registers function of the Schneider Electric Modicon M580 controller. An unauthenticated attacker can send a specially crafted UMAS command to cause the device to enter a non-recoverable fault state, stopping all remote communications and process logic until a physical power cycle.

Jared Rittle Follow

Originally disclosed on Cisco Talos

High 7.5 View original

An exploitable denial of service vulnerability exists in the UMAS Read System Coils and Registers functionality of the Schneider Electric Modicon M580 Programmable Automation Controller firmware version SV2.80. A specially crafted UMAS command can cause the device to enter a non-recoverable fault state, resulting in a…

Jared Rittle, on Cisco Talos

The full write-up lives on its author's site

It belongs to its author, so we link to it rather than copy it. The other two tabs are our own rewrites, checked against it.

Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.

How it worked

Root cause

Likely an uncaught exception when processing a malformed UMAS Read System Coils and Registers command, leading to a non-recoverable fault.

Impact

The device enters a non-recoverable fault state, causing a complete stoppage of remote communications and process logic execution, requiring a physical power cycle to recover.

What the attacker needed

Network access to TCP port 502; no authentication required

The fix

The vendor patched the vulnerability; the report does not describe the fix details.

How it was found

  1. Connect to the device on TCP port 502.
  2. Send a UMAS Read System Coils and Registers command with malformed data.
  3. The device enters a non-recoverable fault state and stops all remote communications.

Explained by bugbounty.wiki with AI from the original and checked against quotes from it; it can still be wrong. Read the original before relying on a detail.

Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.

This report describes a flaw in an industrial controller (a device that runs machinery). An attacker can send a malformed network message to the controller without logging in, and the device crashes so badly that it must be manually power-cycled to work again. This is called a denial of service because it stops the device from doing its job.

What is DoS?

A request that exhausts resources or crashes a component. Many programs forbid testing it; reports usually show it from code, not by attacking.

More by Jared Rittle

View all

64 more disclosed reports, best first.

More from Cisco Talos

View all

The newest disclosed reports for this program.

Similar reports

View all

Same bug class and techniques, clearest first.

Denial of service

The lesson behind this report.

A request that exhausts resources or crashes a component. Many programs forbid testing it; reports usually show it from code, not by attacking.