A REST API endpoint on the Modicon M580 controller can be made to fault when a client holds a PLC reservation under a long registered name. An unauthenticated attacker could send a crafted request that puts the device into a non-recoverable fault, stopping all remote communications and process logic until a physical power cycle.
Originally disclosed on Cisco Talos
An exploitable denial of service vulnerability exists in the UMAS REST API getcominfo functionality of the Schneider Electric Modicon M580 Programmable Automation Controller firmware version SV2.80. A specially crafted HTTP request can cause the device to enter a non-recoverable fault state, resulting in a complete…
The full write-up lives on its author's site
It belongs to its author, so we link to it rather than copy it. The other two tabs are our own rewrites, checked against it.
Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.
How it worked
Root cause
Likely an uncaught exception in the getcominfo handler when it processes a client registered name of 0x34 bytes or more, which the text classifies as CWE-248.
Impact
The device may enter a non-recoverable fault where all remote communications and process logic stop, requiring a physical power cycle; in other cases only the HTTP server becomes unresponsive.
What the attacker needed
Network access to the device; no authentication needed; client name of at least 0x34 bytes
How it was found
- Open a TCP connection to the device's Modbus port.
- Send a reservation request carrying a registered client name of at least 0x34 bytes.
- Request the getcominfo REST endpoint over HTTP.
- Observe the request timing out, which usually means the device has faulted.
Explained by bugbounty.wiki with AI from the original and checked against quotes from it; it can still be wrong. Read the original before relying on a detail.
Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.
A programmable logic controller (PLC) is the industrial computer that runs machinery. This one has a small web service that reports who currently holds a reservation on the device. If that name is long enough, asking the web service about it can crash the controller so it stops talking to anything until someone walks over and power-cycles it.
What is DoS?
A request that exhausts resources or crashes a component. Many programs forbid testing it; reports usually show it from code, not by attacking.