Skip to content
DoS Advisory Intermediate CVE-2018-7855

Schneider Electric Modicon M580 UMAS set breakpoint denial-of-service vulnerability

A denial-of-service vulnerability exists in the UMAS set breakpoint functionality of the Schneider Electric Modicon M580 controller. An unauthenticated attacker can send a specially crafted UMAS command to cause the device to enter a non-recoverable fault state, stopping all remote communications and requiring a physical power cycle.

Jared Rittle Follow

Originally disclosed on Cisco Talos

High 7.5 View original

An exploitable denial-of-service vulnerability exists in the UMAS set breakpoint functionality of the Schneider Electric Modicon M580 Programmable Automation Controller, firmware version SV2.70. A specially crafted UMAS command can cause the device to enter a non-recoverable fault state, resulting in a complete…

Jared Rittle, on Cisco Talos

The full write-up lives on its author's site

It belongs to its author, so we link to it rather than copy it. The other two tabs are our own rewrites, checked against it.

Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.

How it worked

Root cause

Likely an uncaught exception in the UMAS set breakpoint handler when processing certain parameter values, leading to a non-recoverable fault.

Impact

The device enters a non-recoverable fault state, causing a complete stoppage of remote communications and process logic execution, and requires a physical power cycle to recover.

What the attacker needed

Network access to port 502; no authentication required

The fix

The vendor patched the vulnerability.

How it was found

  1. Establish a TCP connection to the device on port 502.
  2. Send a UMAS TAKE_PLC_RESERVATION command to obtain a session identifier.
  3. Send a UMAS SET_BREAKPOINT command (function code 0x60) with crafted parameters.
  4. The device enters a non-recoverable fault state and stops responding.

Explained by bugbounty.wiki with AI from the original and checked against quotes from it; it can still be wrong. Read the original before relying on a detail.

Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.

This report describes a flaw in an industrial controller (a programmable automation controller) that can be crashed by sending a malformed network message. The message is part of a management protocol called UMAS, and when the device receives it with certain parameters, it enters an unrecoverable error state. The attacker does not need to log in, and the only way to recover is to physically power-cycle the device.

What is DoS?

A request that exhausts resources or crashes a component. Many programs forbid testing it; reports usually show it from code, not by attacking.

More by Jared Rittle

View all

64 more disclosed reports, best first.

More from Cisco Talos

View all

The newest disclosed reports for this program.

Similar reports

View all

Same bug class and techniques, clearest first.

Denial of service

The lesson behind this report.

A request that exhausts resources or crashes a component. Many programs forbid testing it; reports usually show it from code, not by attacking.