Schneider Electric Modicon M580 UMAS set breakpoint denial-of-service vulnerability
A denial-of-service vulnerability exists in the UMAS set breakpoint functionality of the Schneider Electric Modicon M580 controller. An unauthenticated attacker can send a specially crafted UMAS command to cause the device to enter a non-recoverable fault state, stopping all remote communications and requiring a physical power cycle.
Originally disclosed on Cisco Talos
An exploitable denial-of-service vulnerability exists in the UMAS set breakpoint functionality of the Schneider Electric Modicon M580 Programmable Automation Controller, firmware version SV2.70. A specially crafted UMAS command can cause the device to enter a non-recoverable fault state, resulting in a complete…
The full write-up lives on its author's site
It belongs to its author, so we link to it rather than copy it. The other two tabs are our own rewrites, checked against it.
Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.
How it worked
Root cause
Likely an uncaught exception in the UMAS set breakpoint handler when processing certain parameter values, leading to a non-recoverable fault.
Impact
The device enters a non-recoverable fault state, causing a complete stoppage of remote communications and process logic execution, and requires a physical power cycle to recover.
What the attacker needed
Network access to port 502; no authentication required
The fix
The vendor patched the vulnerability.
How it was found
- Establish a TCP connection to the device on port 502.
- Send a UMAS TAKE_PLC_RESERVATION command to obtain a session identifier.
- Send a UMAS SET_BREAKPOINT command (function code 0x60) with crafted parameters.
- The device enters a non-recoverable fault state and stops responding.
Explained by bugbounty.wiki with AI from the original and checked against quotes from it; it can still be wrong. Read the original before relying on a detail.
Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.
This report describes a flaw in an industrial controller (a programmable automation controller) that can be crashed by sending a malformed network message. The message is part of a management protocol called UMAS, and when the device receives it with certain parameters, it enters an unrecoverable error state. The attacker does not need to log in, and the only way to recover is to physically power-cycle the device.
What is DoS?
A request that exhausts resources or crashes a component. Many programs forbid testing it; reports usually show it from code, not by attacking.