Schneider Electric Modicon M580 UMAS strategy transfer denial-of-service vulnerability
A denial-of-service vulnerability exists in the UMAS strategy transfer functionality of the Schneider Electric Modicon M580 controller. An attacker can send unauthenticated commands to cause the device to enter a recoverable fault state, stopping normal execution.
Originally disclosed on Cisco Talos
An exploitable denial-of-service vulnerability exists in the UMAS strategy transfer functionality of the Schneider Electric Modicon M580 programmable automation controller firmware version SV2.70. A specially crafted UMAS command can cause the device to enter a recoverable fault state, resulting in a stoppage of…
The full write-up lives on its author's site
It belongs to its author, so we link to it rather than copy it. The other two tabs are our own rewrites, checked against it.
Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.
How it worked
Root cause
Likely the device does not properly validate the uploaded strategy file's integrity, leading to an uncaught exception during the END_STRATEGY_UPLOAD step.
Impact
The device enters a recoverable fault state, stopping normal execution and removing the existing strategy; recovery requires the programming software UnityPro.
What the attacker needed
Network access to the device; no authentication required
The fix
The vulnerability was fixed by the vendor in a patch released on 2019-05-14.
How it was found
- Send a TAKE_PLC_RESERVATION request to obtain a session and privilege.
- Send an INITIALIZE_UPLOAD command to indicate a new program will follow.
- Send the first block of data using an UPLOAD_BLOCK command.
- Send a command with function code 0x6D.
- Send the strategy in chunks using UPLOAD_BLOCK, resending the first block.
- Send an END_STRATEGY_UPLOAD request to indicate the last block has been sent.
Explained by bugbounty.wiki with AI from the original and checked against quotes from it; it can still be wrong. Read the original before relying on a detail.
Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.
This is a bug in an industrial controller that lets anyone on the network crash it by sending a series of special commands. The device stops working until it is manually restarted with programming software.
What is DoS?
A request that exhausts resources or crashes a component. Many programs forbid testing it; reports usually show it from code, not by attacking.