Schneider Electric Modicon M580 UMAS write system coils and holding registers denial-of-service vulnerability
A specially crafted UMAS command to write system coils and holding registers with an out-of-range offset causes the Modicon M580 controller to enter a non-recoverable fault state, stopping all remote communications and process logic. An unauthenticated attacker can send this command to cause a denial of service.
Originally disclosed on Cisco Talos
An exploitable denial-of-service vulnerability exists in the UMAS write system coils and holding registers functionality of the Schneider Electric Modicon M580 Programmable Automation Controller, firmware version SV2.70. A specially crafted UMAS command can cause the device to enter a non-recoverable fault state…
The full write-up lives on its author's site
It belongs to its author, so we link to it rather than copy it. The other two tabs are our own rewrites, checked against it.
Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.
How it worked
Root cause
Likely the device does not properly validate the offset field in the UMAS write command, allowing a write beyond the intended memory range and causing an uncaught exception.
Impact
The device enters a non-recoverable fault state, stopping all remote communications and process logic execution, and requires a physical power cycle to recover.
What the attacker needed
Network access to the device on port 502; no authentication required
The fix
The vendor patched the vulnerability.
How it was found
- Connect to the device on TCP port 502.
- Send a UMAS WRITE_SYSTEM_COILS_AND_HOLDING_REGISTERS command with object type 0x21 and an offset value of 0xffffff.
- The device enters a non-recoverable fault state, requiring a physical power cycle.
Explained by bugbounty.wiki with AI from the original and checked against quotes from it; it can still be wrong. Read the original before relying on a detail.
Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.
This report describes a flaw in an industrial controller (a PLC) that runs factory equipment. By sending a specially formed network message, an attacker can make the device crash and stop working until someone physically restarts it. No password is needed, so anyone who can reach the device on the network can cause this.
What is DoS?
A request that exhausts resources or crashes a component. Many programs forbid testing it; reports usually show it from code, not by attacking.