SATisfying our way into remote code execution in the OPC UA industrial stack
Two vulnerabilities in the Unified Automation OPC UA C++ SDK: an out-of-bounds read in string conversion leaks heap memory, and an integer overflow in argument replacement leads to a heap overflow. An authenticated high-privilege attacker could chain these to achieve remote code execution on the demo server.
Published on jfrog.com
The JFrog Security team recently competed in the Pwn2Own Miami 2022 hacking competition which focuses on Industrial Control Systems (ICS) security. One of our research targets for the competition was the Unified Automation C++-based OPC UA Server SDK.
The full write-up lives on its author's site
It belongs to its author, so we link to it rather than copy it. The other two tabs are our own rewrites, checked against it.
Not written yet. The AI write-up for this write-up has not been written yet. The Original tab links to the source.
How it worked
Root cause
Likely two separate coding errors: a loop that skips bytes without checking for the string terminator, and an integer overflow in a size calculation for a buffer.
Impact
An authenticated high-privilege attacker could achieve remote code execution, though the exploit's success rate was low and required multiple attempts.
What the attacker needed
High-privilege authentication; ability to write to a string node; ability to upload PubSub configuration
The fix
The vulnerabilities were fixed in version 1.7.7 of the SDK.
How it was found
- Authenticate to the OPC UA server with high privileges.
- Write a specially crafted string to a node to trigger the out-of-bounds read.
- Read the node to leak heap memory and bypass ASLR.
- Upload a PubSub configuration with crafted field names to trigger the heap overflow.
- Overwrite a function pointer in a heap object to redirect execution to a ROP chain.
Explained by bugbounty.wiki with AI from the original and checked against quotes from it; it can still be wrong. Read the original before relying on a detail.
Not written yet. The AI write-up for this write-up has not been written yet. The Original tab links to the source.
OPC UA is a protocol used in industrial systems to read and write data values called nodes. A string conversion function reads past the end of a string and returns extra memory to the client, leaking information. A separate function that fills in placeholders in a format string miscalculates a buffer size, allowing an attacker to write beyond the buffer and potentially run their own code.
What is RCE?
Running the attacker's code on the target's servers: through command or code injection, unsafe deserialisation or template injection.