Skip to content
DoS Advisory Intermediate CVE-2017-12089

Allen Bradley Micrologix 1400 Series B Ladder Logic Program Download Device Fault Denial of Service Vulnerability

A denial of service vulnerability exists in the program download functionality of Allen Bradley Micrologix 1400 Series B PLCs. An unauthenticated attacker can send a specially crafted packet to force the device into a fault state, halting operations.

Jared Rittle Follow

Originally disclosed on Cisco Talos

High 8.6 View original

An exploitable denial of service vulnerability exists in the program download functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a device fault resulting in halted operations.

Jared Rittle and Patrick DeSantis, on Cisco Talos

The full write-up lives on its author's site

It belongs to its author, so we link to it rather than copy it. The other two tabs are our own rewrites, checked against it.

Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.

How it worked

Root cause

Likely the PLC does not properly handle an incomplete program download sequence, leaving it in a state that leads to a fault.

Impact

An unauthenticated attacker can cause the PLC to fault and halt operations, potentially disrupting industrial processes.

What the attacker needed

Network access to the PLC; PLC in REMOTE keyswitch mode

How it was found

  1. Connect to the PLC on the EtherNet/IP port (default 44818).
  2. Register a session with the PLC.
  3. Set the CPU state to program mode.
  4. Send the 'Execute Command List' packet used during a standard download process, but do not send the 'download complete' packet.
  5. The PLC halts in the download state for one minute and then transitions into the fault state.

Explained by bugbounty.wiki with AI from the original and checked against quotes from it; it can still be wrong. Read the original before relying on a detail.

Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.

This is a denial-of-service bug in an industrial controller (a PLC). The device expects a series of messages when a new program is downloaded; if an attacker sends only the first message and not the final one, the device gets stuck and then faults, stopping the machine it controls. No login is needed to send this message.

What is DoS?

A request that exhausts resources or crashes a component. Many programs forbid testing it; reports usually show it from code, not by attacking.

More by Jared Rittle

View all

5 more disclosed reports, best first.

More from Cisco Talos

View all

The newest disclosed reports for this program.

Similar reports

View all

Same bug class and techniques, clearest first.

Denial of service

The lesson behind this report.

A request that exhausts resources or crashes a component. Many programs forbid testing it; reports usually show it from code, not by attacking.