Skip to content
DoS Advisory Intermediate CVE-2017-12093

Allen Bradley Micrologix 1400 Series B PLC Session Communication Insufficient Resource Pool Denial of Service Vulnerability

The PLC only supports ten concurrent sessions and evicts the oldest connection when a new one arrives. An unauthenticated attacker could flood the device with session registration packets, repeatedly pushing out legitimate engineering sessions so the operator loses access to the PLC.

Jared Rittle Follow

Originally disclosed on Cisco Talos

Medium 5.3 View original

An exploitable insufficient resource pool vulnerability exists in the session communication functionality of Allen Bradley Micrologix 1400 Series B Firmware 21.2 and before. A specially crafted stream of packets can cause a flood of the session resource pool resulting in legitimate connections to the PLC being…

Jared Rittle and Patrick DeSantis, on Cisco Talos

The full write-up lives on its author's site

It belongs to its author, so we link to it rather than copy it. The other two tabs are our own rewrites, checked against it.

Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.

How it worked

Root cause

Likely the session table has a fixed small capacity and, when full, evicts the oldest session rather than rejecting new unauthenticated requests, so an attacker can continually displace legitimate sessions.

Impact

An unauthenticated attacker could repeatedly disconnect legitimate engineering sessions, denying the operator access to the PLC, although the PLC itself continues to run in its previous state.

What the attacker needed

Network access to the PLC's EtherNet/IP port; no authentication required

How it was found

  1. Open a TCP connection to the PLC's EtherNet/IP port.
  2. Repeatedly send session registration packets in a loop.
  3. Observe that an existing engineering session is disconnected.
  4. Reconnect as the legitimate user and see the session pushed out again while the flood continues.

Explained by bugbounty.wiki with AI from the original and checked against quotes from it; it can still be wrong. Read the original before relying on a detail.

Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.

This device is an industrial controller that lets a limited number of people connect to it at once. When the limit is reached, it drops the oldest connection to make room for a new one. An attacker can keep opening new connections so the real operator is always the one dropped, and the operator cannot stay connected to manage the machine.

What is DoS?

A request that exhausts resources or crashes a component. Many programs forbid testing it; reports usually show it from code, not by attacking.

More by Jared Rittle

View all

5 more disclosed reports, best first.

More from Cisco Talos

View all

The newest disclosed reports for this program.

Similar reports

View all

Same bug class and techniques, clearest first.

Denial of service

The lesson behind this report.

A request that exhausts resources or crashes a component. Many programs forbid testing it; reports usually show it from code, not by attacking.