Skip to content
Access control Advisory Intermediate CVE-2017-14462CVE-2017-14463CVE-2017-14464CVE-2017-14465CVE-2017-14466CVE-2017-14467CVE-2017-14468CVE-2017-14469CVE-2017-14470CVE-2017-14471CVE-2017-14472CVE-2017-14473

Allen Bradley Micrologix 1400 Series B Unauthenticated Data/Program/Function File Improper Access Control Vulnerability

The Allen Bradley Micrologix 1400 Series B PLC allows unauthenticated read and write access to data, program, and function files via CIP encapsulated PCCC commands. An attacker can disclose sensitive information, modify settings, overwrite ladder logic, force I/O, and trigger faults.

Jared Rittle Follow

Originally disclosed on Cisco Talos

Critical 10.0 View original

An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings…

Jared Rittle and Patrick DeSantis, on Cisco Talos

The full write-up lives on its author's site

It belongs to its author, so we link to it rather than copy it. The other two tabs are our own rewrites, checked against it.

Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.

How it worked

Impact

An attacker could read sensitive information (including the master password and ladder logic), modify settings, overwrite ladder logic, force I/O, and trigger faults, potentially disrupting industrial processes.

What the attacker needed

Network access to the PLC; keyswitch in REMOTE or PROG (for some actions)

How it was found

  1. Connect to the PLC's EtherNet/IP port (default 44818).
  2. Register a session with the PLC.
  3. Send CIP encapsulated PCCC commands with function codes for reading (0xa1, 0xa2) or writing (0xa7, 0xa9, 0xaa, 0xab) to target files.
  4. For write operations, craft packets to modify ladder logic, force I/O, change network settings, or clear the master password.
  5. For read operations, request specific data files to retrieve the master password or ladder logic.

Explained by bugbounty.wiki with AI from the original and checked against quotes from it; it can still be wrong. Read the original before relying on a detail.

Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.

A programmable logic controller (PLC) is an industrial computer that controls machinery. This report found that the PLC does not require a password for many file operations, so anyone who can reach it on the network can read or change its program and settings. That could let an attacker disrupt physical processes or steal the password.

What is Access control?

A user can do something their role should not allow: reach an admin function, act on a feature they have not paid for, or skip a permission check. IDOR is the special case where the object belongs to someone else.

More by Jared Rittle

View all

5 more disclosed reports, best first.

More from Cisco Talos

View all

The newest disclosed reports for this program.

Similar reports

View all

Same bug class and techniques, clearest first.

Broken access control

The lesson behind this report.

A user can do something their role should not allow: reach an admin function, act on a feature they have not paid for, or skip a permission check. IDOR is the special case where the object belongs to someone else.