Allen Bradley Micrologix 1400 Series B SNMP-Set Processing Incorrect Behavior Order Denial of Service Vulnerability
A specially crafted SNMP set request to a specific OID causes the Allen Bradley Micrologix 1400 Series B PLC to reboot without performing a firmware update, leading to denial of service. An attacker can send a single packet to trigger the reboot, causing downtime.
Originally disclosed on Cisco Talos
An exploitable denial of service vulnerability exists in the processing of snmp-set commands of the Allen Bradley Micrologix 1400 Series B FRN 21.2 and below. A specially crafted snmp-set request, when sent without associated firmware flashing snmp-set commands, can cause a device power cycle resulting in downtime for…
The full write-up lives on its author's site
It belongs to its author, so we link to it rather than copy it. The other two tabs are our own rewrites, checked against it.
Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.
How it worked
Root cause
Likely the device processes the SNMP set command to enter flashing mode without verifying that the necessary firmware flashing commands are also present, causing an unintended reboot.
Impact
An attacker can cause the device to power cycle, resulting in downtime for the device.
What the attacker needed
Privileged SNMP community string; network access to device SNMP port
How it was found
- Set the SNMP OID .1.3.6.1.4.1.95.2.3.1.1.1.1.0 to the integer value 2 using an SNMP set request.
- Send the request to the device's SNMP port (default 161) using a privileged community string (e.g., 'wheel').
- The device reboots without performing any firmware flashing, causing downtime.
Explained by bugbounty.wiki with AI from the original and checked against quotes from it; it can still be wrong. Read the original before relying on a detail.
Not written yet. The AI write-up for this report has not been written yet. The Original tab links to the source.
This report describes a flaw in an industrial controller (a PLC) that manages machinery. By sending a special network message that normally starts a firmware update, an attacker can make the device restart unexpectedly, which stops the machinery it controls. The attacker needs a password-like community string, but a known backdoor string exists.
What is DoS?
A request that exhausts resources or crashes a component. Many programs forbid testing it; reports usually show it from code, not by attacking.